NA2XSEY Three Core Cable,AL/XLPE/CTS/PVC Cable,6/10KV 8.7/15KV 12/20KV 18/30KV

Applications

The cables are mainly used for: 

· Indoors and in cable ducts

· Outdoors,underground and in water

· in power supply stations

· Transformer stations

· Industrial Plants

 Due to the good laying characteristic, this cable can also be installed in difficult line guideways.

The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliabilities.

 

 For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)


Share:

Details

AL/XLPE/CTS/PVC Cable

 Medium voltage three core cable is suitable for use in power networks, in fixed installation outdoors in cable ducts or directly in the ground. Cable operational stability is enhanced because of very low dielectric loss factor, excellent insulation property of XLPE and firm bonding with conductor screen and insulation screen of semi-conductive material (extruded in one process), which makes it widely used in transformer stations, electric power plants and industrial plants. 

Construction 

NA2XSEY Three Core Cable,AL/XLPE/CTS/PVC Cable,6/10KV  8.7/15KV  12/20KV  18/30KV

DescriptionsNA2XSEY Three Core MV Power Cable

ConductorAluminum, Class2Circular compacted conductors

Conductor Screen: Non-metallic,semi-conducting compound

Insulation: Cross-linked polyethylene XLPE

Insulation Screen: Non-metallic,semi-conducting compound

Metallic Screen: Copper Tape

Filler: Non-hygroscopic Material

Binder Tape: Non-hygroscopic Material

Outer Sheath: Polyvinyl Chloride PVC&Polyethylene PE&LSZH

Physical Properties

Operating Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Nominal VoltagesU0/U 1.8/3kV , 6/10 kV, 12/20 kV, 18/30 kV

Technical Data

Three Core Cable(NA2XSEY)-6/10KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx703.42.55327500.443183174
3Cx953.42.75834000.32222208
3Cx1203.42.76137000.253255236
3Cx1503.42.864 43500.206289263
3Cx1853.42.96747000.164326295
3Cx2403.43.1 7456000.125394347
3Cx3003.43.3 7966500.100 450390
3Cx4003.43.58372500.0778522444
Three Core Cable(NA2XSEY)-8.7/15KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx704.52.75832500.443183174
3Cx954.52.86339000.32222208
3Cx1204.52.96642000.253255236
3Cx1504.5369 47000.206289263
3Cx1854.53.1 7353000.164326295
3Cx2404.53.3 7963000.125394347
3Cx3004.53.4 8471500.100 450390
3Cx4004.53.78897000.0778522444
Three Core Cable(NA2XSEY)-12/20KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx705.52.86336500.443183174
3Cx955.52.96742000.32222208
3Cx1205.53.0 7047000.253255236
3Cx1505.53.1 72.0 52000.206289263
3Cx1855.53.3 7858000.164326295
3Cx2405.53.4 8369000.125394347
3Cx3005.53.6 8877000.100 450390
3Cx4005.53.89382000.0778522444
Three Core Cable(NA2XSEY)-18/30KV,19/33KV
No. of cores and nominal cross sectionThickness of InsulationThickness of sheathApprox. Overall DiameterApprox. WeightMax. DC Resistance of conductor(20℃)Current Carrying Capacity
mm2mmmmmmkg/kmΩ/kmin air(A)in ground(A)
3Cx708.03.27549000.443183174
3Cx958.03.37955000.32222208
3Cx1208.03.4 8260000.253255236
3Cx1508.03.5 85.0 65000.206289263
3Cx1858.03.6 8972000.164326295
3Cx2408.03.8 9584000.125394347
3Cx3008.04.0 10095000.100 450390



Contact Us Now